Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
SITOP SEL1200-1400
20
Manual, 06.2019, A5E46496083-1-76
Remote reset (RST)
④
:
Alternatively, the reset can be performed using a remote reset signal (RST)
④
. The non-
isolated 24 V input (referred to the "0 V" terminal of the module) can be used at terminal
"RST". A reset is executed for an input level of > 15 V.
Note
The rising edge of the remote reset signal is evaluated, i.e. for an additional remote reset
signal, initially a voltage level of 13 V must be fallen below.
Using a remote reset signal at terminal "RST" all outputs that were shut down electronically
due to an overload are again reset. Prerequisite: The output is ready to be reset, i.e. the
electronic overload shutdown occurred longer than 20 s ago (LED of the output flashes red).
Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically shut down. Before carrying out a reset, remove the cause of the overload to
prevent a new shutdown.
Summary of Contents for SITOP SEL1200
Page 8: ...Safety instructions SITOP SEL1200 1400 8 Manual 06 2019 A5E46496083 1 76 ...
Page 26: ...Mounting removal SITOP SEL1200 1400 26 Manual 06 2019 A5E46496083 1 76 ...
Page 46: ...Safety approvals EMC 7 3 EMC SITOP SEL1200 1400 46 Manual 06 2019 A5E46496083 1 76 ...
Page 48: ...Ambient conditions SITOP SEL1200 1400 48 Manual 06 2019 A5E46496083 1 76 ...
Page 50: ...Environment SITOP SEL1200 1400 50 Manual 06 2019 A5E46496083 1 76 ...