SITOP PSU8200 1ph
Manual, 11.2014, C98130-A7633-A1-3-7629
33
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The SITOP PSU8200 1ph (6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0) power
supply is designed for connection to a 1-phase AC line supply with a rated voltage of
120/230 V AC, 50/60 Hz.
Figure 5-1
Line connection for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
SITOP PSU8200 1ph (6EP1336-3BA10) power supplies are designed to be connected to a
1-phase AC line voltage or to 2 line conductors of three-phase line supplies (TN, TT or IT
system according to VDE 0100 T 300 / IEC 364-3) with a rated voltage of 120-230 V AC,
50/60 Hz or a DC voltage.