SITOP PSU8200 1ph
Manual, 11.2014, C98130-A7633-A1-3-7629
25
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails according to EN 60715. The device must
be mounted vertically in such a way that the input terminals and the output terminals are at
the bottom to ensure correct cooling.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Output current as a function of the ambient temperature and mounting height
Figure 4-1
6EP3333-8SB00-0AY0 standard mounting position
Figure 4-2
6EP3334-8SB00-0AY0 standard mounting position