Applications
SITOP PSU6200 1ph
70
Manual, 03.2019, A5E44623264-1-76
9.3
Protection against short-time voltage dips
For a drop in the line-side supply voltage, the 24 V power supply still maintains the output
voltage for a short time in the millisecond range (see Chapter Technical data (Page 43)).
For line supplies that manifest frequent brief voltage dips, in order to increase the power
supply reliability, it may make sense to increase the line buffering time in the device using an
additional SITOP PSE201U buffer module.
The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in
parallel to the power supply output (Figure 9-4 Buffering brief power failures using the SITOP
PSE201U buffer module (Page 70)). The buffer time is 200 ms at 40 A up to 1.6 s for a load
current of 5 A. This time can be increased a multiple number of times by connecting buffer
modules in parallel; the maximum buffer time is 10 s.
You can find additional information at:
SITOP PSE201U manual (
https://support.industry.siemens.com/cs/ww/en/view/41129219
Figure 9-3
Buffering brief power failures using the SITOP PSE201U buffer module