Safety, approvals, EMC
7.4 EMC
SITOP PSU6200 1ph
64
Manual, 03.2019, A5E44623264-1-76
7.4
EMC
6EP3323-7SB00-0AX0 (12 V/7 A)
6EP3324-7SB00-3AX0 (12 V/12 A)
6EP3333-7LB00-0AX0 (24 V/3,7 A)
6EP3333-7SB00-0AX0 (24 V/5 A)
6EP3334-7SB00-3AX0 (24 V/10 A)
6EP3336-7SB00-3AX0 (24 V/20 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
80 … 1000 MHz 10 V/m
1400 … 2000 MHz 10 V/m
2000 … 2700 MHz 10 V/m
895 … 905 MHz and 1.89 GHz 10 V/m
High-speed transient disturbance
variables (burst)
EN 61000-4-4
2 kV at line connections
1 kV at DC output
Surge voltages
EN 61000-4-5
2 kV symmetrical at the line connections
4 kV asymmetrical at the line connections
500 V symmetrical/asymmetrical on DC output cables
High-frequency fields
EN 61000-4-6
10 V; 0.15 … 80 MHz
Magnetic fields
EN 61000-4-8
Not applicable
Voltage dips
EN 61000-4-11
100% for 20 ms,
60% for 200 ms,
30% for 500 ms
Voltage interruptions
EN 61000-4-11
100% for 5000 ms
Emitted interference
EN 55022
Class B
Line harmonics limitation
EN 61000-3-2
Class A
Generic standards
EN 61000-6-2
Immunity for industrial environments
EN 61000-6-3
Emission for residential areas
Summary of Contents for SITOP PSU6200
Page 8: ...Notes on safety SITOP PSU6200 1ph 8 Manual 03 2019 A5E44623264 1 76 ...
Page 22: ...Mounting removal SITOP PSU6200 1ph 22 Manual 03 2019 A5E44623264 1 76 ...
Page 42: ...Installation 5 2 Output side connection SITOP PSU6200 1ph 42 Manual 03 2019 A5E44623264 1 76 ...
Page 74: ...Environment SITOP PSU6200 1ph 74 Manual 03 2019 A5E44623264 1 76 ...