4
Order No.: 3ZX1012-0SE38-1AA1
Fig. 3:
Operation
V
max
Maximum actuation speed 1.5 m/s
F
min
Minimum force in direction of actuation 10 N
The safety position switch can be operated only with its
associated triple-coded actuator.
The initial direction of actuation can be either linear or
radial.
Note:
The operating mechanism can
only
be adjusted
through 4 x 90 ° if the actuator is
inserted
.
Do not use the position switch as a stop!
Switch - slow-action switch with NO contacts and
positively driven NC contacts
(connection designations as per EN 50013).
Safety information about the actuator
In the interests of maintaining adequate safety, the actua-
tors are only allowed to be purchased and used in conjunc-
tion with the associated safety switch.
The position switch and the actuator should be assembled
in such a way that the actuator can be inserted into the
operating mechanism without applying any significant lat-
eral force.
The actuator is only allowed to be handed over to suitably
qualified persons with the necessary know-how and experi-
ence in dealing with the relevant standards and safety
rules. The objective is to guarantee optimum protection for
persons and machines and to enable instances of misuse
to be identified immediately. If the actuator enters into the
possession of unauthorized persons, the safety device may
be manipulated and accidents can occur.
Please pass this information on to all customers who pur-
chase separate actuators, to ensure that these actuators
are only made available to authorized persons.
Fig. 4:
Circuit states
Fig. 5:
Sketched circuit diagram
Fig. 6:
LEDs
Versions 3SE.8..-.XX20, 3SE.8..-.XX32 only
Fig. 7:
System description/suggested application
The protective door is closed while the machine is operat-
ing. The actuator is inserted in the safety switch and
locked. The enable circuits on the evaluation module are
closed and the enable circuit on the control module is
open. It is necessary to reach behind the protective grille
for maintenance purposes. The machine must be switched
off by the operator beforehand.
This causes the enable circuits on the evaluation module to
open and the power level of the machine to be deactivated.
Since the dangerous movement of the machine is not
stopped immediately, the safety switch must not enable the
actuator until the machine overtravel has finished. This is
ensured by a suitable control module, such as a zero-
speed relay or a delay module. The safety contacts (posi-
tively driven NC contacts
) prevent the machine from
restarting if the protective door is open. The additional NO
contacts can be used as signaling contacts. In this case,
these contact functions serve to improve the availability of
the machine rather than safety.
If suitable evaluation modules are available, the NO con-
tacts can be incorporated in the safety circuit as additional
monitoring devices.
The contact pair used for monitoring is positively switched
by the actuator, so that the position of the protective door is
sensed directly. The contact pair used for monitoring the
locking device is positively connected to the locking bar so
that a failure of the tumbler device is detected by the fail-
safe controller. The integrated fail-safe principle prevents
the locking device from being set to the locked position if
the actuator is not yet inserted in the safety switch. This
contact pair can thus also be used to monitor the protective
device. The fact that it is possible for the contact pairs to
monitor each other means that fail-safe controllers up to
Category 3 in accordance with EN 954-1 can be imple-
mented providing they are integrated in suitable safety
concepts.
Degree of protection
IP 67
Rated thermal current I
th
10 A
Ambient temperature
–30 to +70 °C
Rated insulation voltage U
i
250 V
Rated operational current I
e
AC 12: 230 V 10 A,
AC 15: 230 V 4 A,
Magnet operating voltage
DC 24 V,
AC 110 to 130 V,
AC 230 V
ON period ED
100 %
Power rating P
5.2 W
Short-circuit protection
(DIN VDE 0660 Part 200)
DIAZED fuse links
10 A Dz
6 A TDz
Nominal surge voltage strength U
imp
2.5 kV
Rated operational voltage U
e
230 V
Electrical service life
1 mill. operations with contactor
load 3RH11, 3RT10...
Mechanical service life
1 mill. operations
Switching frequency
6 x 103 switching cycles / hour
Shock resistance
30 g / 11 ms
Max. locking force
1400 N according to GS-ET 19
Technical data