2 Functions
330
7UT613/63x Manual
C53000-G1176-C160-2
2.23.1 Demand Measurement Setup
2.23.1.1 Setting Notes
Mean Value Forma-
tion
The synchronisation instant within one hour, the time interval and the time interval for
averaging can be set via parameters.
The selection of the time period for measured value averaging is set with parameter
7611
DMD Interval
in the corresponding setting group from A to D under
MEA-
SUREMENT
. The first number specifies the averaging time window in minutes while
the second number gives the frequency of updates within the time window.
15 Min.,
3 Subs
, for example, means: Time average is generated for all measured values with
a window of 15 minutes. The output is updated every 15/3 = 5 minutes.
Under address
7612
DMD Sync.Time
it can be determined whether the point in time
for averaging selected under address
7611
is to commence on the hour (
On The
Hour
) or is to be synchronised with another point in time (
15 After Hour
,
30
After Hour
or
45 After Hour
).
If the settings for averaging are changed, then the measured values stored in the
buffer are deleted, and new results for the average calculation are only available after
the set time period has passed.
2.23.1.2 Settings
2.23.2 Min/Max Measurement Setup
2.23.2.1 Setting Notes
Resetting of the minimum and maximum values can also be done cyclically, com-
mencing with the preselected starting time. To select this feature, address
7621
MinMax cycRESET
should be set to
YES
. The point in time when reset is to take place
(the minute of the day in which reset will take place) is set at address
7622
MiMa
RESET TIME
. The reset cycle in days is entered at address
7623
MiMa
RESETCYCLE
, and the beginning date of the cyclical process, from the time of the
setting procedure (in days), is entered at address
7624
MinMaxRES.START
.
Addr.
Parameter
Setting Options
Default Setting
Comments
7611
DMD Interval
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub
Demand Calculation Intervals
7612
DMD Sync.Time
On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour
Demand Synchronization Time
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...