2 Functions
206
7UT613/63x Manual
C53000-G1176-C160-2
2.8
Unbalanced Load Protection
Unbalanced load protection (negative sequence protection) detects unbalanced loads
on the system. In addition, this protection function may be used to detect interruptions,
faults, and polarity problems with current transformers. Furthermore, it is useful in de-
tecting phase-to-earth, phase-to-phase, and double phase-to-earth faults with magni-
tudes lower than the maximum load current.
The tripping circuit monitoring is only sensible in three-phase protected objects.
Whereas
PROT. OBJECT
=
1ph Busbar
or
1 phase transf.
(see Functional
Scope, address
105
, section 2.1.3.1) the following settings are not available.
In case of generators and motors, unbalanced loads create counter-rotating fields
which act on the rotor at double frequency. Eddy currents are induced at the rotor
surface leading to local overheating in rotor end zones and slot wedges.
In case of motors with fuses connected in series, a motor operating in single-phase
condition due to operation of a fuse, only generates small and pulsing torque so that
it is soon thermally strained assuming that the torque required by the machine remains
unchanged. In addition, with unbalanced supply voltage it is endangered by thermal
overload. Due to the small negative sequence reaction even small voltage asymme-
tries lead to negative sequence currents.
The negative sequence protection always refers to the three phase currents of the
configured side or measuring location (see „Assigning the Functional Scope“, in Sub-
section 2.1.4).
The unbalanced load protection consists of two definite time stages and one inverse
time stage, The latter may operate according to an IEC or an ANSI characteristic. A
stage with a power-proportional characteristic (negative sequence current) is possible
instead of the inverse time stage.
2.8.1
Function Description
Determination of
Unbalanced Load
The unbalanced load protection of 7UT613/63x filters fundamental components from
applied the phase currents and dissects them into their symmetrical components. Of
this the negative sequence current of the system
I
2
is evaluated. If the largest of the
three phase currents lies above the minimum current
I
-REST
of the one assigned
side or measuring location and all phase currents are smaller than 4 times the rated
current of the assigned side or measuring location, then the comparison of negative
sequence current and setting value can take place.
Definite Time Stages
The definite time characteristic is of two-stage design. When the negative sequence
current exceeds the set threshold
I2>
the timer
T I2>
is started and a corresponding
pickup message is output. When the negative sequence current exceeds the set
threshold
I2>>
of the high-set stage the timer
T I2>>
is started and a corresponding
pickup message is output.
When a delay time is expired trip command is issued.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...