2 Functions
36
7UT613/63x Manual
C53000-G1176-C160-2
2.1.2.3
Information List
2.1.3
Configuration of the Functional Scope
The devices 7UT613/63x contain a series of protective and additional functions. The
scope of hardware and firmware is matched to these functions. Additionally, the
control functions can be in accordance with the system requirements. In addition, in-
dividual functions may be enabled or disabled during configuration, or interaction
between functions may be adjusted. Functions not to be used in the actual
7UT613/63x device can thus be masked out.
Example for the configuration of the scope of functions:
7UT613/63x devices are intended to be used for busbars and transformers. Overload
protection should only be applied on transformers. If the device is used for busbars
this function is set to
Disabled
, for the transformers this function is set to
Enabled
.
The available protection and additional functions can be configured as
Enabled
or
Disabled
. For various functions, a choice may be presented between several
options which are explained below. Functions configured as
Disabled
are not pro-
cessed by the 7UT613/63x. There are no indications, and associated settings
(functions, limit values) are not displayed during detailed settings.
2.1.3.1
Setting Notes
Determination of
the Functional
Scope
Configuration settings can be entered using a PC and the software program DIGSI
and transferred via the front serial port or the rear service interface. The operation via
DIGSI is explained in the SIPROTEC System Description/1/.
In order to change
configuration parameter,
entering of
password no. 7
(for param-
eter set) is required. Without the password, the settings may be read, but may not be
modified and transmitted to the device.
Function scope and, if necessary, the available options are set in the
Function Scope
dialogue box to match plant requirements.
Note
The available functions and default settings depend on the order variant of the device.
Special characteristics are set out in detail below. The annex includes a list of the func-
tions with the suitable protective objects.
No.
Information
Type of In-
formation
Comments
009.0100 Failure Modul
IntSP
Failure EN100 Modul
009.0101 Fail Ch1
IntSP
Failure EN100 Link Channel 1 (Ch1)
009.0102 Fail Ch2
IntSP
Failure EN100 Link Channel 2 (Ch2)
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...