Functions
2.1 General
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
30
If the primary reference voltage and the primary reference current of the protected object are specified, the
device can calculate and issue the percentage operational measured values.
2.1.4.2
Setting Notes
Definition of Nominal Rated Values
At addresses
1101
FullScaleVolt.
and
1102
FullScaleCurr.
, the primary reference voltage (phase-to-phase) and
reference current (phase) of the protected equipment is entered (e.g. motors). If these reference sizes match
the primary nominal values of the VTs and CTs, they correspond to the settings in address
202
and
204
(Section
2.1.2.3). They are generally used to show values referenced to full scale.
2.1.4.3
Settings
The table indicates region-specific default settings.
2.1.4.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
1101
FullScaleVolt.
0.10 .. 800.00 kV
20.00 kV
Measurem:FullScaleVolt-
age(Equipm.rating)
1102
FullScaleCurr.
10 .. 50000 A
400 A
Measurem:FullScaleCur-
rent (Equipm.rating)
No.
Information
Type of Information
Comments
356
>Manual Close
SP
>Manual close signal
420
>Opened Ctrl 2
SP
>Opened Control device 2
421
>Opened Ctrl 3
SP
>Opened Control device 3
422
>Closed Ctrl 2
SP
>Closed Control device 2
423
>Closed Ctrl 3
SP
>Closed Control device 3
424
Open Ctrl 2
OUT
Open control device 2
425
Close Ctrl 2
OUT
Close control device 2
426
Open Ctrl 3
OUT
Open control device 3
427
Close Ctrl 3
OUT
Close control device 3
533
IL1 =
VI
Primary fault current Ia
534
IL2 =
VI
Primary fault current Ib
535
IL3 =
VI
Primary fault current Ic
561
Man.Clos.Detect
OUT
Manual close signal detected
4601
>Brk Aux NO
SP
>Breaker contact (OPEN, if breaker is open)
4602
>Brk Aux NC
SP
>Breaker contact (OPEN, if breaker is closed)