Technical Data
4.1 General Device Data
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
111
PPS/IRIG-B
4.1.5
Electrical Tests
Regulations
Insulation Test
EMC Tests for Immunity (Type Tests)
Connection
ST
multimode optical fiber G50
m/125
m, G62.5
m/125
m
Standards:
see also individual tests
Merging unit
Bay units
IEC 60255
EN 60255/EN 50263
DIN 57435/DIN EN 50263
IEC TS 61000-6-5
IEC/EN 61000-4
IEC 60694
IEC 61850-3
ANSI/IEEE Std C37.90
IEC 61010-1
VDE 0435
IEC 60870
EN 60870
DIN EN 60870
IEC TS 61000-6-5
IEC/EN 61000-4
IEC 60694
IEC 61850-3
Standards:
IEC 60255-27 and IEC 60870-2-1
Voltage test (component test) all circuits except for
auxiliary voltage, binary inputs and communication
interfaces
2.5 kV; 50 Hz
Voltage test (component test) auxiliary voltage and
binary inputs
DC 3.5 kV
Voltage test (component test) only isolated commu-
nication interfaces (A and B)
500 V; 50 Hz
Impulse voltage test (type test), all process circuits
(except for communication interfaces) against inter-
nal electronics
6 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
Impulse voltage test (type test), all process circuits
(except for communication interfaces) against each
other and against the grounding terminal category
III
5 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
Standards:
IEC 60255-6 and -22, (product standards)
IEC/EN 61000-6-2
VDE 0435
For additional standards, see the individual tests
1 MHz test, class III IEC 60255-22-1, IEC 61000-4-
18, IEEE C37.90.1
2.5 kV (peak); 1 MHz;
= 15 µs; 400 surges per s; test
duration 2 s; R
i
= 200
Electrostatic discharge, class IV
IEC 60255-22-2, IEC 61000-4-2
8 kV contact discharge; 15 kV air discharge; both polari-
ties; 150 pF; R
i
= 330