Functions
2.1 General
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
18
Special Features
Most settings are self-explanatory. The special cases are described as follows:
At address 0
369
VT Con Type
, you can specify the connection type of the voltage inputs. If you are using normal
voltage transformers, select
CONVENTIONAL
.
With 0
459
Syscon MU Configuration
, you can define whether the communication parameter configured with
System configurator or not.
With 0
461
PhaseIndepRatio
, you can specify if the independent CT/VT ratio is supported for each channel.
Under address
0700 GOOSE-Stop
,
you can select whether the GOOSE function of the IEC 61850 protocol is
active or not. If
GOOSE-Stop
is set to
YES
, you can activate the GOOSE function via a binary input during the
operation.
Under address
0357 SV-Stop
, you can select whether the SV function of the IEC 61850 protocol is active or not.
If
SV-Stop
is set to
YES
, you can activate the SV function via a binary input during the operation. The address
0357 SV-Stop
is visible only when the address
0459 SysConMUConf
is set as
Enabled
.
2.1.1.3
Settings
2.1.1.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
0104
OSC. FAULT REC.
Disabled
Enabled
Disabled
Oscillographic Fault
Records
0357
SV-Stop
YES
NO
NO
SV-Stop
0459
SysConMUConf
Enabled
Disabled
Disabled
MU Configuration via
IEC61850 System Con-
figurator
0461
PhaseIndepRatio
Enabled
Disabled
Disabled
Phase Independent Ratio
0640
Start image DD
image 1
image 2
image 3
image 4
image 5
image 6
image 1
Start image Default
Display
0700
GOOSE-Stop
YES
NO
NO
GOOSE-Stop
No.
Information
Type of In-
formation
Comments
-
>Light on
SP
>Back Light on
-
Reset LED
IntSP
Reset LED
-
DataStop
IntSP
Stop data transmission
-
Test mode
IntSP
Test mode
-
Feeder gnd
IntSP
Feeder GROUNDED
-
Brk OPENED
IntSP
Breaker OPENED