16-bit value (hex.)
16-bit value (dec.)
Factor
Current value [mA]
0x1999
6553
0.00305
20 mA
0x0CCC
3277
10 mA
0x0000
0
0 mA
0xF333
-3277
-10 mA
0xE666
-6553
-20 mA
Underrange
-
up to -23.5 mA
Underflow
-
Deactivation
Table 12-59 Measured values in the "temperature measurement" operating mode
16-bit value (hex.)
16-bit value (dec.)
Factor
Temperature value [°C]
Overflow
0x0A28
2590
0.1
259° C
0x03E8
1000
100° C
0x01F4
500
50° C
0x0000
0.0
0° C
0xFE0C
-500
-50° C
0xFC18
-1000
-100° C
0xF830
-2000
-200° C
Underflow
Note
If a Pt100 element is accidentally not connected in this operating mode and an input voltage
higher than 0.25 V is connected, the analog module automatically switches to the "No operating
mode" operating mode and resets the gain factor to "1". This is signalized in Status Word 0
(channel-specific) in the input image. In addition, a corresponding error code is output in the
diagnostics slot at a counter value of "2".
In the case of operation without a Pt100 element, a slightly negative voltage may be applied,
which results in an error/fault status for the module. Here, the "PNFault" LED and the status byte
1 are to be observed.
Analog outputs
Table 12-60 Measured values in the "voltage output" operating mode
16-bit value (hex.)
16-bit value (dec.)
Factor
Voltage value [V]
Overflow
-
Deactivation
Overrange
-
Up to 10.5 V
Connectable components
12.3 PP 72/48D PN 2/2A PN
NCU 1740
152
Equipment Manual, 10/2021, A5E51087503B AA