Parameter
ID
Unit
Default
Min
Max
Description
Ground Fault
Limit
7106
%
40.0
0.0
100.0
Set the level above which the drive issues
an input ground fault alarm.
Ground Fault
Time Const
7107
sec
0.2
0.001
2.0
Set the time constant of filter used for
averaging input neutral voltage when de‐
tecting a ground fault.
Dedicated Input
Protect
7108
Off
Input protection uses dedicated inputs
and outputs controlled by NXGpro code.
Options are:
• Off
• On
Input Breaker
Open Time
7125
sec
0.4
0.02
0.5
Set the maximum expected opening time
for the input breaker. This value is used for
Tamper Resistant Input Protection.
Test IP Interrupt
Time
7126
Function
Test the input breaker interruption time
response time. Input breaker will open
during test.
Drive Has Input
Breaker
7127
Yes
Indicates that drive has input breaker that
is under NXGpro software control. Op‐
tions are:
• Yes
• No
Table 6-90
Single Phasing Menu (7010) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
SPD prop gain
7020
0.0
0.0
10.0
Single phase detector PI regulator propor‐
tional gain term.
SPD integral
gain
7030
0.001
0.0
1.0
Single phase detector PI regulator integral
gain term.
SPD threshold
7040
%
50.0
0.0
100.0
Regulator output level below which an
alarm is generated.
Table 6-91
Drive Security Reset and Secure System Keys (for USB flash disk)
Parameter
ID
Description
Reset Credentials
7748
Reset DCR password for use with ToolSuite
Create Factory Key
7749
Create nxgrecover.factory secure key file on USB
Create Restore Key
7750
Create nxgrecover secure key file on USB
Create Emergency Key
7751
Create nxgemergency secure key file on USB
Create Update Key
7752
Create nxgupdate secure key file on USB
Parameter 7748, Reset Credentials, resets the ToolSuite nxgproplus user login password to
"nxgproplus".
Spare controllers are usually shipped with the following password scheme, unless otherwise
specified:
DCR serial # example: Y20010001aa!
Parameter Assignment/Addressing
6.16 Options for Drive Protect Menu (7) - part 2
Control Manual
Operating Manual, A5E50491925A
159
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......