Result
The test is passed if the components required for the specified housing degree of protection are
available.
3.1.3
Electrical cabinet components
Fundamentals
A visual inspection is made to see whether the electrical cabinet components are installed as
defined in the layout diagram and/or circuit diagram.
Test procedure
1. The customer selects electrical cabinet components by random sampling.
2. The selected electrical cabinet components are visually checked to ensure that they are
correctly installed and marked.
Result
The test is passed if the selected electrical cabinet components are installed as specified in the
layout diagram and/or circuit diagram.
3.1.4
Cable installation
Fundamentals
Visual and mechanical checks are made to ensure that cables and conductors have been
installed correctly and are connected correctly according to the circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
2. The following is inspected:
– Are the cables firmly connected?
– Have edge protectors been attached to sharp edges?
– Are the cables routed according to the circuit diagram?
Result
The inspection is passed if the cable installation does not exhibit any deficiencies and matches
the information in the circuit diagram.
Tests
3.1 Visual inspection
SINAMICS DCM 6RN F03
Reference Manual Rev.201902141527 SINAMICS DCM
17
Summary of Contents for SINAMICS DCM 6RN
Page 2: ...14 02 2019 15 27 V8 00 ...
Page 6: ...Table of contents SINAMICS DCM 6RN F03 6 Reference Manual Rev 201902141527 SINAMICS DCM ...
Page 8: ...Introduction SINAMICS DCM 6RN F03 8 Reference Manual Rev 201902141527 SINAMICS DCM ...
Page 24: ...Index SINAMICS DCM 6RN F03 24 Reference Manual Rev 201902141527 SINAMICS DCM ...
Page 25: ......
Page 28: ......
Page 30: ......