E-48
SIMEAS Q80 7KG8080
Power Quality Recorder SIMEAS Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 09.02.2011
Evaluations / Standards
Voltage quality as per EN 50160
IEC 61000-4-30 Ed.2 class A compliant for the following:
- Frequency
- Magnitude of Supply Voltage
- Flicker
- Voltage Dips, Swells, Interruptions
- Unbalance
- Harmonics, Interharmonics
- Mains Signaling
- Time clock uncertainty
- Flagging
IEC 61000-4-15
IEC 61000-4-7
Power calculation as per
DIN 40110-1 and –2
Data search and data comparison
across multiple measurements
IEC 61000-4-30 Ed.2 measurement accuracy and range
The accuracy and range specifications matches the IEC 61000-4-30 Ed.2 standard.
Parameter
Uncertainty
Measuring Range
Influence Quantity Range
Frequency
±
10 mHz
40 Hz to 57,5 Hz
50 Hz to 69 Hz
40 Hz to 57,5 Hz
50 Hz to 69 Hz
Magnitude of supply
±
0.1 %
10 % to 200 %
10% to 200 %
Flicker
±
5 %
0.2 to 10 Pst
0 to 20 Pst
Dips and Swells
±
0.2 %
-
-
Interruptions
-
-
-
Unbalance
±
0.15 %
0.5 % to 5 %
0 % to 5 %
Voltage Harmonics
±
5 % U
harm
(U
harm
>1 %)*
±
0,05 % U
nom
(U
harm
<1 %)
-
-
Mains signalling
voltage
±
5 % U
sgn
(U
sgn
>3 %)
±
0,15 % U
nom
(1 %< U
sgn
<3 %)
0 % to 9 %
0 % to 9 %
*U
nom
= Operating voltage
,
U
harm
= Amplitude of the harmonics (RMS values)