E-73
Technical specs and terminal configuration
Power Quality Recorder SIMEAS Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 09.02.2011
14.1.4 Digital outputs
4 digital outputs
Parameter
typ.
min. / max.
Test conditions / Remarks.
channel / bits
4
mechanical closer
terminal connection
screw terminal 14 to 24 AWG
0,2 mm² to 2,5mm²
American Wire Gauge
for rigid and flexible lines
insulation test voltage
3,6 kV
RMS
50 Hz Sinus; 10 sec
electrical safety
rating /
measurement category
degree of pollution
250 V / CAT III
2
according EN 61010-1
according IEC 60664
switching time
5 ms
<8 ms
max. switching power
<1000 VA
switching voltage
>1 V
DC
<250 V
RMS
min. switching voltage at 1mA
max. switching current
< 1 A
<4 A
250 V~ cos
j
=1.0 ... 0.4
250 V~ cos
j
=1.0
contact impedance
<50 m
W
Description of the
digital outputs of SIMEAS Q80 7KG8080
.
37