E-54
SIMEAS Q80 7KG8080
Power Quality Recorder SIMEAS Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 09.02.2011
11.1.2.4 Measurement channel overview
X = always present
Xi = present if current is measured
Xt = present of the associated trigger was activated
O = able to be switched on/ off (Optional)
- = not present
Bold and italic entries are required for the EN 50160.
Measurement intervals: the interval written in bold print is to be used for compliance with the standard EN 50160.
For all channels, it’s possible to calculate a histogram and the cumulative frequency subsequently.
Measurement
Measurement intervals
and comments
3-phase
current
4-wire
3-phase
current
3-wire
Single-line
Voltage
3 s, 10 s, 1 min, 5 min, 10 min, 15 min, 30
min, 1 h, 2 h
X
X
X
Ux_rms_mean
Ux_rms_min
Ux_rms_max
Ux_rms_redu
Ux_THD_mean
Ux_harmn_mean
with x=1..4; n=1..50
Ux_frz_mean
with z=1..10
Mean of the voltage RMS value
Minima in the aggregation interval
Maxima in the aggregation interval
Reduced time plot (maximum resolution: 1/2
cycle)
THD ( voltage total harmonic distortion)
Voltage harmonics
Arbitrary monitored fixed frequencies
(e.g. interharmonics)
X
O
O
X
X
X
O
X
O
O
X
X
X
O
X
O
O
X
X
X
O
Current
3 s, 10 s, 1 min, 5 min, 10 min, 15 min, 30
min, 1 h, 2 h
O
O
O
Ix_rms_mean
Ix_rms_min
Ix_rms_max
Ix_rms_redu
Ix_THD_mean
Ix_harmn_mean
with x=1..4; n=1..50
Ix_frz_mean
with z= 1..10
Mean of the voltage RMS value
Minima in the aggregation interval
Maxima in the aggregation interval
Reduced time plot
THD ( current total harmonic distortion)
Current harmonics
Arbitrary monitored fixed frequencies
Xi
O
O
Xi
Xi
Xi
O
Xi
O
O
Xi
-
-
O
Xi
O
O
Xi
Xi
Xi
O
Frequency
3 s, 10 s, 30 s, 1 min, 5 min, 10 min
X
X
X
Frequency
Frequency_histogram
System frequency
Histogram of frequency
X
X
X
X
X
X
Symmetry
3 s, 10 s, 1 min, 5 min, 10 min, 15 min, 30
min, 1 h, 2 h
X
X
-
Unbalance_rms
SymmetryZero_rms
SymmetryPositive_rms
SymmetryNegative_rms
Zero sequence system
Positive sequence system
Negative sequence system
X
X
X
X
X
X
X
-
-
-
-