70
Insulation type of inputs and outputs
Signal inputs (current)
Reinforced,
max. 600 V AC, Cat II or
max. 300 V AC, Cat III
Signal inputs (voltage)
Protective impedance,
max. 600 V AC, Cat II or
max. 300 V AC, Cat III
Power supply
Reinforced,
max. 230 V AC/250V DC, Cat II
Output contacts
Reinforced,
max. 230 V AC/250V DC, Cat II
Reference conditions
The stated error limits apply for
reference conditions
Input current I
i
I
IN
± 1%
Input voltage U
i
U
IN
± 1%
Frequency f
i
45 ... 65 Hz
Waveform
Sinus, harmonic distortion
≤
5%
Ambient temperature T
A
23 °C ± 1 °C
Auxiliary voltage U
H
U
HN
± 1%
Warm-up time
≥
15 min
External fields
no
Environmental conditions
The device is designed for indoor
use only
Ambient Temperature
According to IEC 60688
Operating Temperature Range 32° F to 131° F (0° C to 55° C)
Storage Temperature Range
-13° F to 158° F (-25° C to 70° C)
Max. rel. humitidy
80 % for temperatures up to 31 °C
decrease linearly to 50 % at 40 °C
Max. altitude above sea level 2000 m
Pollution degree
2, no condensation
Summary of Contents for SIMEAS P 7KG7100
Page 32: ...29 1 12 3 Gerätevariante 7KG7610 Achtung Erdung muss an SIMEAS P immer angeschlossen sein V ...
Page 41: ...38 Einphasen Wechselstrom Dreileiter Drehstrom gleiche Belastung ...
Page 42: ...39 Dreileiter Drehstrom beliebige Belastung Vierleiter Drehstrom gleiche Belastung ...
Page 55: ...52 Notizen ...
Page 93: ...90 Single phase AC current Three wire three phase balanced ...
Page 94: ...91 Three wire three phase unbalanced Four wire three phase balanced ...
Page 107: ...104 Notes ...