69
Dielectric test,
routine test, 2 s
according to IEC 61010-1
Signal inputs (current to
current and current to
voltage)
2.2 kV; AC
Current inputs to serial
interface, PG, binary outputs
and power supply
2.2 kV; AC
Power supply, serial interface
and binary outputs mutually
3.1 kV; DC
Power supply to PG
3.1 kV; DC
Voltage inputs, binary outputs
to PG
1.35 kV; AC
Serial interface to PG
500 V; AC
Additional for 7KG7610:
Binary inputs and binary/relay
outputs to PG
2.2 kV; 50 Hz; AC
Analog inputs and analog
outputs to PG
500 V; 50 Hz; AC
Summary of Contents for SIMEAS P 7KG7100
Page 32: ...29 1 12 3 Gerätevariante 7KG7610 Achtung Erdung muss an SIMEAS P immer angeschlossen sein V ...
Page 41: ...38 Einphasen Wechselstrom Dreileiter Drehstrom gleiche Belastung ...
Page 42: ...39 Dreileiter Drehstrom beliebige Belastung Vierleiter Drehstrom gleiche Belastung ...
Page 55: ...52 Notizen ...
Page 93: ...90 Single phase AC current Three wire three phase balanced ...
Page 94: ...91 Three wire three phase unbalanced Four wire three phase balanced ...
Page 107: ...104 Notes ...