65
2.9
Technical Data
Input signals
Only for connection to AC systems
Max. system voltage
Y 400 /
∆
690 V
Overload 20%
Frequency of fundamental
component
40 ... 65 Hz
Frequency range f
i
+/- 5 Hz, min. > 30% U
IN
Waveform
Sinusoidal or distorted up to the
21st harmonic
AC current inputs
I
I
3 current inputs
Input current I
i
1 A; 5 A
Continuous overload
Surge withstand capability
10 A
100 A for 1s
Power consumption per phase 83 µVA at 1 A ; 2.1 mVA at 5 A
AC voltage inputs
U
I
3
voltage
inputs
Input voltage U
I
100/110 V; 190 V; 400 V; 690 V (L-L)
Continuous overload capacity
Surge withstand capability
1.5 x U
I
2.0 x U
I
Input resistance (L - N)
2.663 M
Ω
Power consumption per phase 120 mW (U
LE
= 400 V)
Binary inputs
(optional, only 7KG7610)
Max. input voltage
300 V DC
Current consumption for high
level
1.8 mA
Threshold voltage low
≤
10 V
Threshold voltage high
≥
19 V
Signal delay
max. 3 ms
Analog inputs
(optional, only 7KG7610)
Measuring range
0 to 20 mA DC
Input range
0 to 24 mA DC
Input resistance
50
Ω
±
0.1%
Accuracy
0.5% of the measuring range limit
Summary of Contents for SIMEAS P 7KG7100
Page 32: ...29 1 12 3 Gerätevariante 7KG7610 Achtung Erdung muss an SIMEAS P immer angeschlossen sein V ...
Page 41: ...38 Einphasen Wechselstrom Dreileiter Drehstrom gleiche Belastung ...
Page 42: ...39 Dreileiter Drehstrom beliebige Belastung Vierleiter Drehstrom gleiche Belastung ...
Page 55: ...52 Notizen ...
Page 93: ...90 Single phase AC current Three wire three phase balanced ...
Page 94: ...91 Three wire three phase unbalanced Four wire three phase balanced ...
Page 107: ...104 Notes ...