63
2.8
Measured Values
Measured values
Measuring
path
1
Menu
Tolerances
2
Voltage
L1-N, L2-N,
L3-N, (N-E)
d
a
h
±
0.2%
Voltage
L1-L2, L2-L3,
L3-L1,
Σ
3
d
a
h
±
0.2%
Current
L1, L2, L3, N,
Σ
3
d
a
h
±
0.2%
Active power P
+ import, - export
L1, L2, L3,
Σ
d
a
h
±
0.5%
Reactive power Q
+ cap, - ind
L1, L2, L3,
Σ
d
a
h
±
0.5%
Apparent power S
L1, L2, L3,
Σ
d
a
h
±
0.5%
Power factor |cos
ϕ
|
4
L1, L2, L3,
Σ
d
a
h
±
0.5%
Active power factor
cos
ϕ
4
L1, L2, L3,
Σ
d
a
h
±
0.5%
Phase angle
4
L1, L2, L3,
Σ
d
a
h
±
2°
Frequency
5
L1-N
d
a
h
±
10 mHz
Active power import
L1, L2, L3,
Σ
d
a
±
0.5%
Active power export
L1, L2, L3,
Σ
d
a
±
0.5%
Active power absolute
L1, L2, L3,
Σ
d
a
±
0.5%
Active power saldo
Σ
d
a
±
0.5%
Reactive power cap
L1, L2, L3,
Σ
d
a
±
0.5%
Reactive power ind
L1, L2, L3,
Σ
d
a
±
0.5%
Summary of Contents for SIMEAS P 7KG7100
Page 32: ...29 1 12 3 Gerätevariante 7KG7610 Achtung Erdung muss an SIMEAS P immer angeschlossen sein V ...
Page 41: ...38 Einphasen Wechselstrom Dreileiter Drehstrom gleiche Belastung ...
Page 42: ...39 Dreileiter Drehstrom beliebige Belastung Vierleiter Drehstrom gleiche Belastung ...
Page 55: ...52 Notizen ...
Page 93: ...90 Single phase AC current Three wire three phase balanced ...
Page 94: ...91 Three wire three phase unbalanced Four wire three phase balanced ...
Page 107: ...104 Notes ...