Installing and putting a TIM into operation
5.4 Options for attachment and settings of the TIM 3 and TIM 4 variants
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
201
Pinout of the X3 RJ-12 Western jack for the MD4 integrated modem
The X3 connector of the integrated MD4 modem is designed as a 6-pin RJ-12 Western jack.
The pinout is shown in the following table.
Table 5-36 Pinout of the X3 RJ-12 Western jack for the MD4 integrated modem
Illustration
Pin no.
Signal name
Signal direction
Remark
1
-
2
TX-
Output
Along with TX+
3
RX-
Input
4
RX+
Input
5
TX+
Output
Along with TX-
6
5
4
3
2
1
6
-
Standard connecting cable for the integrated MD4 modem
The connecting cable 6NH7700-4AR60 is supplied with every TIM module with an integrated
MD4 modem. This allows the MD4 modem integrated in the TIM to be connected to an
ISDN-S0 telephone outlet.
The connecting cable can also be ordered as a spare under the number shown.
Table 5-37 Standard connecting cable for the integrated MD4 modem
Order no.
Description
Illustration
6NH7700-4AR60
Connecting cable with RJ-12 and RJ-45 Western plug to
connect an MD4 modem (RJ-12) with an ISDN-S0 outlet
(RJ-45). The cable is also suitable for an MD4 integrated
in a TIM.
Cable length 6 m
5-
5-
Note
It is best to hold the cable just below the RJ-12 plug. This makes it easier to insert the plug
than if you hold the RJ-12 plug itself. When inserting it, make sure that you can hear the RJ-
12 connector click into place!
The following table shows the pinout of the two connectors for the standard connecting cable
mentioned above.