Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
SINAUT ST7 Station control system - System Manual
50
System Manual, 05/2007, C79000-G8976-C178-06
TIM 43 / TIM 43D
Construction
•
Module format
•
Dimensions (W x H x D) in mm
•
Weight
•
Compact module for S7-300, double width
•
80 x 125 x 120
•
Approx. 300 g
Degree of protection
IP 20
Configuration
•
Software for PG
•
Software for CPU (optional)
•
Storage of TIM configuration data
•
SINAUT ST7 configuration software
for PG
•
SINAUT TD7 block library for CPU
•
on internal TIM flash memory
TIM can be operated in the role
•
Station
•
Node station
•
Master station
•
Yes
•
Yes
•
Yes
Number of TIM 43/43D modules per S7-CPU or
PC
Several, number depends on the communication
resources of the S7-CPU or of the PC
Local communication in the rack of an S7-300
•
Over backplane bus with the S7-300-CPU
•
Over backplane bus with other TIMs in the
rack
•
Over MPI port of the S7-300-CPU
2)
with other
CPUs, TIMs, and/or PCs
•
Possible using TD7onCPU
1)
•
Possible
•
Possible over TD7onCPU (for S7-300 and
S7-400) and S7 communication (for
ST7cc/ST7sc and TIMs)
Local communication in standalone mode
•
Over MPI port of the CPU with CPUs, other
TIMs and/or PCs
•
Possible over TD7onCPU (for S7-300 and
S7-400) and S7 communication (for
ST7cc/ST7sc and TIMs)
Work memory required on the S7 CPU
At least 20 KB; actual requirements depend on
the amounts of data and range of functions
Message memory on TIM
•
Number of messages
•
Buffered
•
Approx. 10,000 messages
•
No
Transmission protocols
Selectable protocols
•
SINAUT ST7
•
SINAUT ST1
Mode with dedicated line/wireless network
•
SINAUT ST7 protocol
•
SINAUT ST1 protocol
•
- Polling
- Polling with time slots
- Multi-master polling with
time slots
•
- Polling
- Polling with time slots
Mode in dial-up network
•
SINAUT ST7 protocol
•
SINAUT ST1 protocol
•
Spontaneous
•
Spontaneous