Introduction
1.5.3 Supported Fiber Optic Cables
Follow these recommendations for copper data cabling in high electrical noise envi-
ronments:
• Data cable lengths should be as short as possible, preferably 3 m (10 ft) in
length. Copper data cables should not be used for inter-building communica-
tions.
• Power and data cables should not be run in parallel for long distances, and
should be installed in separate conduits. Power and data cables should intersect
at 90° angles when necessary to reduce inductive coupling.
• Shielded/screened cabling can be used when required. Care should be taken to
avoid the creation of ground loops with shielded cabling.
1.5.3
Supported Fiber Optic Cables
The following fiber optic cable types are supported under the stated conditions.
Distance (m)
Cable Type
Wavelength (nm)
Modal Band-
width (MHz·km)
100Base-FX
1000Base-SX
10GBase-SR
850
200
—
275
33
OM1 (62.5/125)
1300
500
2000
—
—
850
500
—
550
82
OM2 (50/125)
1300
500
2000
—
—
850
1500
—
550
300
1300
500
2000
—
—
850
3500
—
550
400
1300
500
2000
—
—
Laser optimized.
8
RUGGEDCOM RST2228P
Installation Manual, 12/2019, C79000-G8976-1403-05