Certification
6.1.6 Other Approvals
A copy of the Material Declaration is available online at
try.siemens.com/cs/ww/en/view/109738831
6.1.6
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61850-3
General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2488F has passed the following EMC and environmental tests.
EMC Type Test for IEC 61850-3
Note
• In the case of an all fiber port configuration, this product meets all Class 2 re-
quirements. Otherwise, all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during
which disturbance errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during
which no disturbance errors will occur.
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
± 4 kV @ 2.5
and 5 kHz
Note
DC Power Ports
AC Power Ports
± 4 kV @ 2.5
and 5 kHz
IEC 61000-4-4
Burst (Fast
Transient)
Earth Ground Ports
± 4 kV @ 5 kHz
IEC 61000-4-5
Surge
Signal Ports
± 4 kV Line-
to-Earth
4
RUGGEDCOM RSG2488F
Installation Manual, 11/2019, C79000-G8976-1351-05
45