Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity Levels
AC Power Ports
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RSG2488F meets Class 2 requirements for an all-fiber configura-
tion and Class 1 requirements for copper ports. Class 1 allows for temporary commu-
nication loss, while Class 2 requires error-free and interrupted communications.
Description
Test Levels
Signal Ports
5 kV (Failsafe Relay Output)
DC Power Ports
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV
DC Power Ports
1.5 kVDC
Dielectric
Strength
AC Power Ports
2 kV
Signal Ports
DC Power Ports
AC Power Ports
± 4 kV @ 2.5 and 5 kHz
Fast Transient
Earth Ground Ports
± 4 kV @ 5 kHz
Signal Ports
2.5 kV Common Mode @ 1MHz
DC Power Ports
Oscillatory
AC Power Ports
2.5 kV Common Mode
1 kV Differential Mode @ 1 MHz
Radiated RFI
Enclosure ports
35 V/m
Enclosure Contact
± 2 kV
± 4 kV
± 8 kV
ESD
Enclosure Air
± 4 kV
± 8 kV
± 15 kV
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-14
Change of Temperature
Test Nb
5 Cycles, -40 to 85°
C (40 to 185° F)
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing)
55 °C (131 °F), 6 Cycles
IEC 60068-2-31
Free Fall
Procedure 1, 2 falls from a
height of 250 mm (9.8 in)
RUGGEDCOM RSG2488F
Installation Manual, 11/2019, C79000-G8976-1351-05
47