6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
DC Power
Ports
± 1.5 kV
x
Earth
Ground Ports
± 2 kV
3
Signal Ports
± 500 V Line-to-Earth
± 500 V Line-to-Line
x
IEC
61000-4-5
Surge
DC Power
Ports
± 500 V Line-to-Earth
± 500 V Line-to-Line
x
Signal Ports
10 V
3
DC Power
Ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
IEC
61000-4-8
Magnetic Field
Enclosure
Ports
40 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-29
Voltage Dips and Interrupts
DC Power
Ports
30% for 0.1 s
60% for 0.01 s
100% for 0.01 s
Signal Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
DC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
Signal Ports
30 V Continuous
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
Ports
30 V Continuous,
300 V for 1s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
Ports
± 15%
4
Signal Ports
2 kV (Fail-Safe
Relay output)
IEC 60255-5
Dielectric Strength
DC Power
Ports
1.5 kV
Signal Ports
5 kV (Fail-Safe
Relay output)
IEC 60255-5
HV Impulse
DC Power
Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS900GPF meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper Ports. Class 1 allows for
34
RUGGEDCOM RS900GPF
Installation Manual, 01/2021, C79000-G8976-1353-05