Functions of the IM 151/CPU
5-17
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Table 5-12 Parameter Blocks, Settable Parameters and Their Ranges for the IM 151/CPU
Parameter Blocks
Range
Settable Parameters
Start date for the OB 10
Year-month-day
Start time for the OB 10
Hours:minutes
Cyclic interrupts
Periodicity of the OB 35 (ms)
1 to 60000
Cycle behavior
Cycle load from communication (%)
10 to 50
Scan cycle monitoring time (ms)
1 to 6000
OB85 call at I/O access error
For each access
For incoming and
outgoing errors
No call
Protection
Level of protection
1: Key switch
2: Write protection
3: Write/read
protection
Mode
Process mode:
permissible cycle
increase (ms)
from 3 to 65535
Test mode
Module parame-
ters
Number of reference junctions
Activated
Module number
Channel number
8
Yes/no
From 5 to 66
0/1
Interference frequency suppression
50 Hz / 60 Hz
DP station address
CPU DP address
1 to 125
When Does the CPU ”Accept” the Parameters?
The CPU accepts the parameters (configuration data) you have set:
After power on or a memory reset of the inserted memory module
After the configuration data has been transferred without errors to the CPU
online in STOP mode
Summary of Contents for SIMATIC IM 151/CPU
Page 6: ...Important Information vi ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 14: ...Contents xiv ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 42: ...ET 200S in the PROFIBUS Network 3 12 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 68: ...Commissioning and Diagnostics 4 26 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 98: ...Technical Specifications 6 8 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 108: ...Cycle and Response Times 7 10 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 190: ...Execution Times of the SFCs and SFBs C 4 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 196: ...Migration of the IM 151 CPU D 6 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...