Commissioning and Diagnostics
4-10
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Diagnosis of DP Functionality Using the “BF” and “SF” LEDs
If the “BF” and “SF” LEDs light up or flash, the ET 200S is not configured correctly.
The table below shows you the possible error indications together with their
meanings and the necessary action.
The table below shows the LED states for DP slave operation. DP functionality is
irrelevant in stand-alone operation, and a BF LED is not activated (there is no LED
for transmission rate detection).
Table 4-4
LEDs for PROFIBUS-DP
”BF”
LED
”SF”
LED
Description
Cause
Error handling
On
On
No connection to the DP
master
Bus connection
interrupted
Master does not exist or
is switched off
SF is on due to station
failure
Check that the
connector for the
PROFIBUS-DP is
inserted correctly.
Check whether the bus
cable to the DP master
is defective.
LED
flashes
On
Parameter assignment
error; there is no data
exchange
Slave not configured or
incorrectly configured
Incorrect but
permissible station
address set
Configured address
areas of the actual
configuration not
identical to the target
configuration
Station failure of a
configured sender in
direct data
communication
DP master does not
exist/is switched off, but
a connection to the
programming
device/OP exists
Check the hardware of
the ET 200S.
Check the configuration
and parameterization of
the ET 200S.
Check the setting for
the configured address
areas for the master
and slave.
*
On
Slave error: impermissible
station address
Impermissible station
address set (0,
126,127,...)
Set station address
differs from the
configured address
Set the PROFIBUS
address in the correct
range using the DIL switch
block in the basic module.
LED
off
On
Slave error: diagnostic
interrupt
Master in STOP
Switch the DP master to
RUN mode.
LED
off
LED
off
Data exchange taking
place
The target configuration
and actual configuration of
the ET 200S match.
*
The status is not relevant.
Summary of Contents for SIMATIC IM 151/CPU
Page 6: ...Important Information vi ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 14: ...Contents xiv ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 42: ...ET 200S in the PROFIBUS Network 3 12 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 68: ...Commissioning and Diagnostics 4 26 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 98: ...Technical Specifications 6 8 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 108: ...Cycle and Response Times 7 10 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 190: ...Execution Times of the SFCs and SFBs C 4 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 196: ...Migration of the IM 151 CPU D 6 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...