B-10
Equipment Manual OP7, OP17
Release 04/99
Remedy:
Cause
Mes-
sage
534
Information message: disk is full.
535
Disk access error.
536
Disk transfer error.
Check the physical connection.
537
Information message: disk is blank.
538
Simultaneous accessing of data record by job and
operator.
Repeat uncompleted accessing ope-
ration.
539
The data records in the RAM for recipe no. x con-
tained errors and have been deleted.
If data records are stored in the Flash
memory they will remain valid.
540
The maximum number of data records has al-
ready been created.
541 ...
550
Specified variable not available on PLC
Change configuration and retransfer.
551
An MPI/PPI connection to the PLC cannot be
established using the specified station address.
Check MPI station addresses and wi-
ring.
570
Variable contains errors: variable name from Pro-
Tool is used as parameter.
Check configuration. Frequently oc-
curs with NC variables and when
multiplexing.
571
S7 system diagnosis/ALARM_S returns error if
OP logs on/off.
CPU operating system out of date.
600
Configuration error: overflow warning at basic
setting 1
601
Configuration error: message logging at basic
setting 1
602
Configuration of remaining buffer space incor-
rect.
Correct the remaining buffer space
and retransfer configuration.
604
Message does not exist.
Configure message.
605
Process link is only configured symbolically.
Change configuration and retransfer.
606
Too many message variables configured.
g
g
607
Data type configured does not exist.
608
The process screen number does not exist.
Change configuration and retransfer.
609
Special object or operator object for message text
does not exist or is not permissible.
g
g
610
Operator object for header or footer does not exist
or is not permissible.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC H li
611
Special operator object for buffer printout does
not exist or is not permissible.
g
, p
MATIC Hotline.
613
Data block not available or too short.
Create data block of required length
on the PLC.
614
No entry present for log (header and footer not
present).
Configure log fully.
Summary of Contents for simatic hmi op7
Page 6: ...iv Equipment Manual OP7 OP17 Release 04 99 Preface ...
Page 11: ...Product Description 1 Functionality 2 Part I Introduction ...
Page 12: ...2 2 Equipment Manual OP7 OP17 Release 04 99 ...
Page 22: ...1 10 Equipment Manual OP7 OP17 Release 04 99 ...
Page 26: ...2 4 Equipment Manual OP7 OP17 Release 04 99 ...
Page 28: ...2 6 Equipment Manual OP7 OP17 Release 04 99 ...
Page 74: ...7 16 Equipment Manual OP7 OP17 Release 04 99 ...
Page 90: ...9 6 Equipment Manual OP7 OP17 Release 04 99 ...
Page 96: ...10 6 Equipment Manual OP7 OP17 Release 04 99 ...
Page 98: ...10 8 Equipment Manual OP7 OP17 Release 04 99 ...
Page 104: ...11 6 Equipment Manual OP7 OP17 Release 04 99 ...
Page 110: ...13 4 Equipment Manual OP7 OP17 Release 04 99 ...
Page 138: ...16 10 Equipment Manual OP7 OP17 Release 04 99 ...
Page 140: ...P 12 Equipment Manual OP7 OP17 Release 04 99 ...
Page 162: ...B 20 Equipment Manual OP7 OP17 Release 04 99 ...