Error messages and troubleshooting
5.2 Error messages
FC 45
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
5-7
Error code
(B#16#..)
Flashing of
ERR LED
Description
19
25x
Previous command is active or buffer overflow.
The user sent a new command to the ASM although the last command
was still active.
•
Active command can only be terminated with an init_run.
•
Before a new command can be started the READY bit must be 1
(exception: init_run).
•
Two FC 45 calls were parameterized with the same
"ASM_address" and "ASM_channel" parameters
•
Two FC 45 calls are using the same Params_DB pointer.
•
Start init_run command after error correction.
•
When command repetition (e.g., fixed code MDS) is used, no data
are fetched from the MDS. The data buffer on the ASM has
overflowed. MDS data have been lost.
1A
–
PROFIBUS DP error occurred.
•
The PROFIBUS DP bus connection was interrupted
–
Wire break on the bus
–
Bus connector on ASM was removed briefly
•
PROFIBUS DP master no longer addresses the ASM
•
Execute an init_run
•
The ASM has detected a message frame interruption on the bus.
The PROFIBUS may have been reconfigured (e.g. with HW
Config).
This error is only indicated when access monitoring has been enabled
in the PROFIBUS configuration.
1B
27x
Only with MOBY F:
•
CRC check in data telegram is incorrect. Checksum error between
ASM and write/read device
•
Interface on ASM or write/read device is defective (hardware
defect).
•
Check wiring of ASM-write/read device cable.
1C
28x
The antenna of the write/read device is turned off. An MDS command
to the ASM was started in this state.
•
Turn on the antenna with the command "antenna on/off."
•
The antenna is turned on (off) and has received an additional turn-
on (turn-off) command.
•
MOBY F: An FFT command was started when antenna was off
(antenna on/off with sub_command = 09).
1D
–
More MDSes are in the transmission window than the SLG is capable
of processing simultaneously.
•
Only 1 MDS can be processed at a time with FC 45.
1E
30x
Error when processing the function
•
The data in UDT 10 are invalid (e.g. write command with length =
0); check UDT 10 and execute init_run
•
ASM hardware defect: ASM receives wrong data during init_run.
•
The "number of bytes" byte does not match the user data length
(see Section "Programming the MOBY-ASM on PROFIBUS DP-
V1").