![Siemens SIMATIC FC 45 Function Manual Download Page 46](http://html.mh-extra.com/html/siemens/simatic-fc-45/simatic-fc-45_function-manual_382128046.webp)
Commissioning
FC 45
4-2
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
When configuring the ASMs, make sure that the I address and the Q address have the same
values. The value in the I address field must be copied later on into the ASM_address
variable in the STEP 7 project. If a MOBY-ASM has more than one channel (e.g. ASM 475 =
2 channels, ASM 454 = 4 channels), the same I address must be used for every channel.
The following figure shows an example of a hardware configuration:
Figure 4-2
Example of a hardware configuration
If the project is downloaded onto the hardware in this state (without the user program), the
SIMATIC CPU and the PROFIBUS should switch to the RUN state. If they don't, continue
with PROFIBUS trouble-shooting (check the PROFIBUS address settings on the ASM
against the configuration in HW Config).