![Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Manual Download Page 62](http://html.mh-extra.com/html/siemens/simatic-et-200sp-f-ai-4xi-0-4-20ma-2-4-wire-hf-series/simatic-et-200sp-f-ai-4xi-0-4-20ma-2-4-wire-hf-series_manual_1265347062.webp)
Interrupts/diagnostic messages
6.3 Diagnostic messages
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
62
Manual, 08/2018, A5E41448857-AB
Supply voltage outside the nominal range
If the supply voltage L+ is outside the specified value range, the DIAG LED flashes and the
module is passivated.
When the voltage is then recovered (level must remain within the specified value for at least
1 minute (see Technical specifications (Page 64): Voltages, Currents, Potentials)), the DIAG
LED stops flashing. The module remains passivated.
Generally applicable information on diagnostics
Information on diagnostics that pertains to all fail-safe modules (for example, readout of
diagnostics functions or passivation of channels) is available in the SIMATIC Safety –
Configuring and Programming
http://support.automation.siemens.com/WW/view/en/54110126
) manual.