Wiring
Distributed I/O Device ET 200R
(4)J31069-D0427-U001-A2-7618
4–7
Wire the coupling plug as shown in the following pin allocation.
Table 4-2
Pin allocation of the coupling plug of the digital inputs/outputs (X0 to X7)
Pin
Allocation
View of Coupling Plug
Wiring Side))
1 24V
(US1)
2 DI/DO
1)
(input/output signal)
3
0 V (US1)
4 DI/DO
1)
(input/output signal)
5 FE/shield
1
5
4
3
2
1) With plug connectors X4 to X7: only DI
Closing unused sockets
Sockets which are not used must be closed with M12 covering caps so that protec-
tion rating IP65 is ensured.
Y connection piece
A Y connection piece permits double connection of actuators or sensors to the in-
puts or outputs of the ET 200R.
We recommend using a Y connection piece when 2 channels per socket of a mo-
dule are being used. The Y connection piece divides the two channels into 2 coup-
ling plugs (for pin allocation see tables 4–3 and 4–4).
a u f E T 2 0 0 R s c h r a u b e n
A n s c h l u s s d e r E i n -
b z w . A u s g ä n g e ü b e r
K u p p l u n g s s t e c k e r M 1 2
A
B
Figure 4-4
Y connection piece
Wire the two M12 coupling plugs for the Y connection piece as specified in the fol-
lowing pin allocation. The allocation of pin 4 of the Y connection piece depends on
the socket of the ET 200R into which you will screw the Y connection piece.