Commissioning and Diagnostics
ET 200iS Distributed I/O Station
7-30
A5E00087831-02
7.8.6
Station Status 1 to 3
Definition
Stations status 1 to 3 provides an overview of the status of a DP slave.
Station Status 1
Table 7-19
Structure of Station Status 1 (Byte 0)
Bit
Meaning
Cause / Remedy
0
1: The DP slave cannot be accessed
by the DP master. The bit on the DP
slave is always "0".
•
Is the correct PROFIBUS address set
on the DP slave?
•
Is the bus connector plugged in?
•
Is the power supply for the DP slave
on?
•
RS-485 repeater set correctly?
•
Has there been a RESET on the DP
slave (off/on)?
1
1: The DP slave is not yet ready for
data exchange.
•
Wait, the DP slave is currently
starting up.
2
1: The configuration data sent to the
DP slave by the DP master do not
match the actual configuration of the
DP slave.
Has the correct station type or correct
configuration of the DP slave been
entered in the configuration software?
3
1: External diagnostic information
exists.
Evaluate the channel-related diagnostic
information, the module status and/or the
channel-related diagnostic information.
As soon as all errors have been
eliminated, bit 3 will be reset. The bit will
be set again when there is a new
diagnostic message in the bytes of the
diagnostic information.
4
1: The requested function is not
supported by the DP slave (for
example, changing the PROFIBUS
addressusing the software).
Check the configuration.
5
1: The DP master cannot interpret the
reply from the DP slave.
Check the bus configuration.
6
1: The DP slave type does not match
the software configuration.
Compare the defined and actual
configuration.
7
1: The parameters for the DP slave
were set by a different DP master (not
by the DP master that currently has
access to the DP slave).
The bit is always 1 if, for example, you
are currently accessing the DP slave
from the programming device or a
different DP master.
The PROFIBUS address of the DP
master that set the parameters for the
DP slave is in the diagnostic byte
"master PROFIBUS address".
Summary of Contents for SIMATIC ET 200iS
Page 20: ...Preface ET 200iS Distributed I O Station 1 6 A5E00087831 02 ...
Page 34: ...Product Overview ET 200iS Distributed I O Station 2 14 A5E00087831 02 ...
Page 84: ...Installation ET 200iS Distributed I O Station 5 18 A5E00087831 02 ...
Page 168: ...Maintenance ET 200iS Distributed I O Station 8 6 A5E00087831 02 ...
Page 184: ...Terminal Modules ET 200iS Distributed I O Station 10 8 A5E00087831 02 ...
Page 188: ...Power Supply Module ET 200iS Distributed I O Station 11 4 A5E00087831 02 ...
Page 320: ...Dimension Drawings ET 200iS Distributed I O Station 17 4 A5E00087831 02 ...
Page 330: ......
Page 332: ...Certifications ET 200iS Distributed I O Station 20 2 A5E00087831 02 ...
Page 333: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 3 ...
Page 334: ...Certifications ET 200iS Distributed I O Station 20 4 A5E00087831 02 ...
Page 336: ...Certifications ET 200iS Distributed I O Station 20 6 A5E00087831 02 ...
Page 337: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 7 20 1 3 Power supply PS ...
Page 338: ...Certifications ET 200iS Distributed I O Station 20 8 A5E00087831 02 ...
Page 339: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 9 20 1 4 4DI NAMUR ...
Page 340: ...Certifications ET 200iS Distributed I O Station 20 10 A5E00087831 02 ...
Page 341: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 11 ...
Page 342: ...Certifications ET 200iS Distributed I O Station 20 12 A5E00087831 02 20 1 5 2DO DC25V 25mA ...
Page 343: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 13 ...
Page 347: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 17 ...
Page 348: ...Certifications ET 200iS Distributed I O Station 20 18 A5E00087831 02 20 1 8 2AI RTD ...
Page 349: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 19 ...
Page 350: ...Certifications ET 200iS Distributed I O Station 20 20 A5E00087831 02 20 1 9 2AI TC ...
Page 351: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 21 ...
Page 352: ...Certifications ET 200iS Distributed I O Station 20 22 A5E00087831 02 20 1 10 2AO I 2AO I HART ...
Page 353: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 23 ...
Page 366: ...Marking ET 200iS Distributed I O Station 21 8 A5E00087831 02 ...
Page 416: ...26 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 417: ...27 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 418: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 419: ...28 Produktinformation RS 485 IS Koppler 6ES7 972 0AC80 0XA0 A5E00207082 01 ...
Page 420: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 02 ...