Commissioning and Diagnostics
ET 200iS Distributed I/O Station
7-46
A5E00087831-02
7.8.13
Diagnostics for Incorrect Module Configuration of the ET 200iS
Incorrect Module Configuration
The following incorrect module configurations in the ET 200iS lead to an ET 200iS
station failure or prevent startup of the data exchange. These reactions are not
dependent on whether or not IM 151-2 parameter "Startup when defined and actual
configuration differ" is enabled:
•
2 modules missing
•
Bus termination module missing
•
Number of modules exceeds maximum configuration
•
Module in the slot 1 missing
•
Backplane bus fault (for example defective terminal module)
Note
If a module is missing (there is a gap) and the ET 200iS power supply is turned off
and then on again, this leads to an ET 200iS station failure.
Diagnostics
You can recognize all the incorrect module configuration states based on the
following diagnostic information:
Table 7-24
Diagnostics for Incorrect Module Configuration of the ET 200iS
ID-Related Diagnostics
Module Status
All the bits from slot 4 to 35 are set
01
B
: "Module error, invalid user data" from
slot 4 to 35
Summary of Contents for SIMATIC ET 200iS
Page 20: ...Preface ET 200iS Distributed I O Station 1 6 A5E00087831 02 ...
Page 34: ...Product Overview ET 200iS Distributed I O Station 2 14 A5E00087831 02 ...
Page 84: ...Installation ET 200iS Distributed I O Station 5 18 A5E00087831 02 ...
Page 168: ...Maintenance ET 200iS Distributed I O Station 8 6 A5E00087831 02 ...
Page 184: ...Terminal Modules ET 200iS Distributed I O Station 10 8 A5E00087831 02 ...
Page 188: ...Power Supply Module ET 200iS Distributed I O Station 11 4 A5E00087831 02 ...
Page 320: ...Dimension Drawings ET 200iS Distributed I O Station 17 4 A5E00087831 02 ...
Page 330: ......
Page 332: ...Certifications ET 200iS Distributed I O Station 20 2 A5E00087831 02 ...
Page 333: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 3 ...
Page 334: ...Certifications ET 200iS Distributed I O Station 20 4 A5E00087831 02 ...
Page 336: ...Certifications ET 200iS Distributed I O Station 20 6 A5E00087831 02 ...
Page 337: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 7 20 1 3 Power supply PS ...
Page 338: ...Certifications ET 200iS Distributed I O Station 20 8 A5E00087831 02 ...
Page 339: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 9 20 1 4 4DI NAMUR ...
Page 340: ...Certifications ET 200iS Distributed I O Station 20 10 A5E00087831 02 ...
Page 341: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 11 ...
Page 342: ...Certifications ET 200iS Distributed I O Station 20 12 A5E00087831 02 20 1 5 2DO DC25V 25mA ...
Page 343: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 13 ...
Page 347: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 17 ...
Page 348: ...Certifications ET 200iS Distributed I O Station 20 18 A5E00087831 02 20 1 8 2AI RTD ...
Page 349: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 19 ...
Page 350: ...Certifications ET 200iS Distributed I O Station 20 20 A5E00087831 02 20 1 9 2AI TC ...
Page 351: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 21 ...
Page 352: ...Certifications ET 200iS Distributed I O Station 20 22 A5E00087831 02 20 1 10 2AO I 2AO I HART ...
Page 353: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 23 ...
Page 366: ...Marking ET 200iS Distributed I O Station 21 8 A5E00087831 02 ...
Page 416: ...26 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 417: ...27 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 418: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 419: ...28 Produktinformation RS 485 IS Koppler 6ES7 972 0AC80 0XA0 A5E00207082 01 ...
Page 420: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 02 ...