Commissioning and Diagnostics
ET 200iS Distributed I/O Station
A5E00087831-02
7-27
Evaluating Interrupts with an S7 DP Master or DPV1 Master
Requirement: You have configured the ET 200iS with STEP 7 (Version 5.1, Service
Pack 2, Hotfix 1 or higher) or PCS 7 (Version 5.2 or higher); in other words,
interrupts are only supported if the ET 200iS functions as an S7-DP slave or DPV1
slave.
If an interrupt occurs, interrupt LPs are called automatically in the CPU of the DP
master (see programming manual System Software for S7-300/S7-400, Program
Design).
Evaluating Interrupts with Other DP Masters
If you operate the ET 200iS with a different DP master or as a DP standard slave,
no interrupts are generated.
Triggering a Diagnostic Interrupt
When an event (for example wire break) enters all leaves the state, the module
triggers a diagnostic interrupt if "Enable: Diagnostic interrupt“ is set.
The CPU interrupts execution of the user program and runs the diagnostic block
OB82. The event that led to the interrupt been triggered is entered in the startup
information of OB82.
Triggering a Hardware Interrupt
If a hardware interrupt occurs, the CPU interrupts execution of the user program
and runs the hardware interrupt block OB40.
The channel of the module that triggered the hardware interrupt is entered in the
startup information of OB40 in the variable OB40_POINT_ADDR. The schematic
below shows the assignment to the bits of the local data double word 8.
•
Analog input modules
31 30 29 28 27 26 25 24
17 16
1 0
Bit-No.
LB 8
LB 9
LB 11
1 1
1 1
LD 8
Below lower limit value channel 1
Below lower limit value channel 0
Above upper limit value channel 1
Above upper limit value channel 0
LB 10
Figure 7-9 Interrupts from Analog Input Modules
Summary of Contents for SIMATIC ET 200iS
Page 20: ...Preface ET 200iS Distributed I O Station 1 6 A5E00087831 02 ...
Page 34: ...Product Overview ET 200iS Distributed I O Station 2 14 A5E00087831 02 ...
Page 84: ...Installation ET 200iS Distributed I O Station 5 18 A5E00087831 02 ...
Page 168: ...Maintenance ET 200iS Distributed I O Station 8 6 A5E00087831 02 ...
Page 184: ...Terminal Modules ET 200iS Distributed I O Station 10 8 A5E00087831 02 ...
Page 188: ...Power Supply Module ET 200iS Distributed I O Station 11 4 A5E00087831 02 ...
Page 320: ...Dimension Drawings ET 200iS Distributed I O Station 17 4 A5E00087831 02 ...
Page 330: ......
Page 332: ...Certifications ET 200iS Distributed I O Station 20 2 A5E00087831 02 ...
Page 333: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 3 ...
Page 334: ...Certifications ET 200iS Distributed I O Station 20 4 A5E00087831 02 ...
Page 336: ...Certifications ET 200iS Distributed I O Station 20 6 A5E00087831 02 ...
Page 337: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 7 20 1 3 Power supply PS ...
Page 338: ...Certifications ET 200iS Distributed I O Station 20 8 A5E00087831 02 ...
Page 339: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 9 20 1 4 4DI NAMUR ...
Page 340: ...Certifications ET 200iS Distributed I O Station 20 10 A5E00087831 02 ...
Page 341: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 11 ...
Page 342: ...Certifications ET 200iS Distributed I O Station 20 12 A5E00087831 02 20 1 5 2DO DC25V 25mA ...
Page 343: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 13 ...
Page 347: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 17 ...
Page 348: ...Certifications ET 200iS Distributed I O Station 20 18 A5E00087831 02 20 1 8 2AI RTD ...
Page 349: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 19 ...
Page 350: ...Certifications ET 200iS Distributed I O Station 20 20 A5E00087831 02 20 1 9 2AI TC ...
Page 351: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 21 ...
Page 352: ...Certifications ET 200iS Distributed I O Station 20 22 A5E00087831 02 20 1 10 2AO I 2AO I HART ...
Page 353: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 23 ...
Page 366: ...Marking ET 200iS Distributed I O Station 21 8 A5E00087831 02 ...
Page 416: ...26 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 417: ...27 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 418: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 419: ...28 Produktinformation RS 485 IS Koppler 6ES7 972 0AC80 0XA0 A5E00207082 01 ...
Page 420: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 02 ...