Commissioning and Diagnostics
3-5
EM 148-FC
Frequency Converter
A5E00065321-03
3.4
Unusual operating conditions
Operation under conditions such as the following can lead to an increased
thermal load on the frequency converter:
High pulse frequency (16 kHz)
Increased supply voltage (500 V)
Low motor frequency (operating speed)
Increased ambient temperature
Constant steep ramping
If a number of these conditions are combined, the frequency converter heats up
considerably. This can lead to the frequency converter being shut down with a
diagnosis of overload. The heat sink of the frequency converter can become very
hot.
To prevent this happening, you can do the following things:
Reduce the pulse frequency
Increase the motor frequency
Reduce the supply voltage
Longer ramp times
Ensure better cooling