Technical Specifications
B-12
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
Table B-7
Climatic ambient conditions
Ambient conditions
Comments
Permissible range
Air pressure
From 1080 to 795 hPa
Corresponds to a height of
-1000 to 2000 m
Contaminant concentration
SO
2
: < 0.5 ppm;
RH < 60 %, no
condensation
H
2
S: < 0.1 ppm;
RH < 60 %, no
condensation
Test: 10 ppm; 4 days
Test: 1 ppm; 4 days
B.1.6
Data on insulation tests, protection class and degree of
protection
Test voltages
The insulating properties are verified in individual testing with the following test
voltages:
Table B-8
Test voltages
Circuits with a rated voltage of U
e
against
other circuits or ground
Test voltage
0 V < U
e
v
50 V
600 VDC, 1 s
Protection class
Protection class I in accordance with IEC 60536, i. e. PE connection to rail is
required!
Protection against solid bodies and water
Protection type IP 20 in accordance with IEC 60529; i.e., protection against contact
with standard probes.
There is not protection against the instrusion of water.
Summary of Contents for Simatic 6ES7 157-0AC80-0 A0 Series
Page 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Page 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Page 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Page 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Page 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Page 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Page 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...