Siemens Building Technologies

Fire Safety

P/N 315-034060-3

A24205-A334-B825

Supervised Input Module (500-034060 / S24235-B112-A2)

Installation Instructions
Model SIM-16

INTRODUCTION

The 

SIEMENS 

Model SIM-16 Supervised Input Module

is a remotely located, general purpose input module. It
provides sixteen input circuits for remote system
monitoring. Each input can be individually programmed
as supervised (dry contacts only) or unsupervised
(general-purpose input). The SIM-16 has two Form C
relays. The relays and the inputs are programmable using
the Zeus Programming Tool.

OPERATION

The SIM-16 is mounted in an enclosure that is remotely
located from the Main Panel. Communication between
the SIM-16 and the NIC-C (Network Interface Card) or
the next CAN module (in CE applications)  is through the
Control Area Network (CAN) bus. Up to 99 SIM-16s can
be used with a single NIC-C or a DAC-NET (in CE
applications).

Each SIM-16 has two 10-position rot ary switches that
are used to set the board address on the CAN which is
a sub-address of the NIC-C or the DAC-NET (in CE
applications).

Every time a change of state of the input is detected, a
unique CAN message is sent to the NIC-C  (DAC-NET).
A CAN message from the NIC-C  (DAC-NET) directed
to the SIM-16 controls the Form C relays.

PRE-INSTALLATION

Rotary Address Switches

 - Set the board address for

each SIM-16 using both of the ten-position rotary
switches located on the board (See Figure 1). Each of
these addresses must be a sub-address of the NIC-C
or the DAC-NET (in CE applications) and must be the same as the addresses
assigned in the Zeus Programming  Tool.

Figure 1
SIM-16 Supervised Input
Module

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

9

10

11

12

13

14

15

16

12

3

4 5 6 7

8

90

12

3

4 5 6 7

8

90

TB2

TB1

P2

S1

S2

P3

TB3

1

1

6

6

TB4

SIM-16

Summary of Contents for SIM-16

Page 1: ... Area Network CAN bus Up to 99 SIM 16s can be used with a single NIC C or a DAC NET in CE applications Each SIM 16 has two 10 position rot ary switches that are used to set the board address on the CAN which is a sub address of the NIC C or the DAC NET in CE applications Every time a change of state of the input is detected a unique CAN message is sent to the NIC C DAC NET A CAN message from the N...

Page 2: ... each NIC C or the CAN bus of the DAC NET in CE applications Each SIM 16 module is shipped with one CCS cable Cable connections for SIM 16 modules are shown in the following t able S N O I T C E N N O C E L B A C 6 1 M I S e l b a C n o i t p i r c s e D r e b m u N t r a P n o i t c e n n o C L C C g n o L E L B A C N A C 6 m c 0 0 1 n i 0 3 r o t c u d n o c 4 1 2 4 3 6 9 9 5 6 K 1 A 5 3 2 4 2 C...

Page 3: ...r limited to NFPA 70 per NEC 760 3 Wiring for TB1 and TB2 is 18 AWG 1 0mm2 min 12 AWG 4mm2 max 4 Wiring for TB3 and TB4 is 26 AWG 0 25mm min 16 AWG 1 5mm2 max 5 CAN network max line resistance 16S 6 Refer to the NIC C Installation Instructions P N 315 033240 A24205 A334 B824 for CAN network termination instructions Figure 2 SIM 16 CAN Bus Connections With An RNI ...

Page 4: ...2 max 5 Wiring for TB3 and TB4 is 26 AWG 0 25mm min 16 AWG 1 5mm2 max 6 5 4 3 2 1 COM N C N O COM N C N O Relay 1 Relay 2 TB3 1 6 TB4 SIM 16 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 TB2 ELECTRICAL RATINGS t n e r r u C e n a l P k c a B V 4 2 0 t n e r r u C V 4 2 l a n i m r e T w e r c S A m 0 2 t u p n i d e s i v r e p u s A m 2 1 y a l e r e v i t c a A m 0 2 t n e r r u C e n a l P k c a B V 2...

Page 5: ...puts unsupervised 2 All inputs power limited to NFPA 70 per NEC 760 3 Wiring for TB1 and TB2 is 18 AWG 1 0mm2 min 12 AWG 4mm2 max 4 All inputs must remain inside the enclosure or within 20 feet 6 5m in rigid conduit 5 In the Zeus Programming Tool select unsupervised for each unsupervised input 6 Supervised and unsuper vised inputs may be mixed on a single SIM 16 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 9 1...

Page 6: ... Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN P N 315 034060 3 A24205 A334 B825 Siemens AG I BT DE FS SYS D 81379 München For CE applications in Cerberus E100 systems refer to Installation InstructionA24205 A334 B844 English orA24205 A334 A844 German ...