Siemens Building Technologies
Fire Safety
P/N 315-034060-3
A24205-A334-B825
5
Figure 5
SIM-16 Supervised Input Wiring
NOTES
1. All inputs supervised.
2. All inputs power limited to
NFPA 70 per NEC 760.
3. Wiring for TB1 and TB2 is
18 AWG
(
1.0mm
2
) min.,
12 AWG
(
4mm
2
) max.
4. Maximum distance 500 feet
(165m) from SIM-16 to
supervised input.
5. In the Zeus Programming
Tool, select supervised for
each supervised input.
6. Supervised and unsuper-
vised inputs may be mixed
on a single SIM-16.
Figure 6
SIM-16 Unsupervised Input Wiring
NOTES
1. All inputs unsupervised.
2. All inputs power limited to
NFPA 70 per NEC 760.
3. Wiring for TB1 and TB2 is
18 AWG
(
1.0mm
2
) min.,
12 AWG
(
4mm
2
) max.
4. All inputs must remain
inside the enclosure or
within 20 feet (6.5m) in
rigid conduit.
5. In the Zeus Programming
Tool, select unsupervised for
each unsupervised input.
6. Supervised and unsuper-
vised inputs may be mixed
on a single SIM-16.
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
9
10
11
12
13
14
15
16
16
15
14
13
12
11
10
9
SIM-16
TB1
TB2
TYPICAL
CONNECTION
(16 PLACES)
*6.8K
*SUPPLIED WITH
THE SIM-16
INPUT #2
INPUT #6
INPUT #16
INPUT #5
INPUT #9
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
9
10
11
12
13
14
15
16
16
15
14
13
12
11
10
9
SIM-16
TB1
TB2
TYPICAL
CONNECTION
(16 PLACES)
INPUT #2
INPUT #1
INPUT #6
INPUT #16
INPUT #5
INPUT #9