Configuration Tool
7-64
©
Siemens AG 2007 All Rights Reserved
SICLOCK
®
TC 400
7.5
Troubleshooting
The following is a list of FAQs and problem solutions for the SICLOCK TC 400
configuration tool.
Table 7-5
Problem solutions for the configuration tool
Question/Problem
Cause/Remedy
Authorization not possible in offline mode
The data does not contain authorization parameters. You must perform an
online authorization.
See
Authorization
(Section 7.2.2).
A connection cannot be established to the device
•
Check whether the correct IP address has been set in the configuration tool.
•
Check whether there is a network connection.
•
Check whether the TCP:2155 port has been released for the connection or
already being used by another application.
See also
Establish/disconnect online connection
(Section 7.2.1).
An event cannot be acknowledged.
This is a persistent message pending on the device.
See also
General functions
(Section 7.2).
No interaction with the device in online mode (hourglass)
The connection to the device has been separated and must be established
again.
See also
Establish/disconnect online connection
(Section 7.2.1).
Parameter cannot be edited
•
The parameter is a display parameter
See
Parameters
(Section 7.3)
•
The current authorization level is too low
See
Authorization
(Section 7.2.2)
•
The parameter does not have a parameter value
In this case, the parameter must be read from the device again.
Parameters and archives are displayed in a language other than the user interface
The language set in the configuration tool is not available in the device.
See
Menus
(Section 7.1)
Parameter is not written during the upload
It is a critical operating parameter
that is explicitly excluded from an upload.
Such parameters must be written individually.
See
Parameters
(Section 7.3) and
Reading parameters / writing parameters
/ resetting parameters to factory settings
(Section 7.3.4).
Summary of Contents for SICLOCK TC 400
Page 1: ...SICLOCK s SICLOCK TC 400 Plant Central Clock Operating Instructions 09 2007 ...
Page 2: ......
Page 6: ...Preface Preface 4 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 Operating Instructions ...
Page 10: ...Table of contents Contents 8 Siemens AG 2007 All Rights Reserved SICLOCK TC400 ...
Page 20: ...Description 2 18 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 26: ...Hardware Description 3 24 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 34: ...Installation 5 32 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 68: ...Configuration Tool 7 66 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 100: ...Parameter Table 10 98 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 110: ...Technical Data 13 108 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 112: ...Dimension Drawing 14 110 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 114: ...Circuit Diagrams 15 112 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 116: ...Spare Parts Accessories 16 114 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 122: ...ESD Guidelines B 120 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 130: ...Glossary D 128 Siemens AG 2007 All Rights Reserved SICLOCK TC 400 ...
Page 133: ......