Service
218
SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
5.2.3 Peripheral
Elements
Startup (step)
RY
ER
Error
Reset, power up or startup initiat-
ed by the higher-level system
element
™
˜
*)
Check code memory (flash
PROM)
™
˜
*)
•
Module is shutdown
•
Startup is aborted
Check data memory (RAM)
™
˜
*)
•
Module is shutdown
•
Startup is aborted
Reception of the parameters from
the higher-level system element
™
™
*)
•
Firmware is shutdown
•
Startup is aborted
Check of the parameter contents
™
™
*)
•
Diagnosis information is set
Startup concluded without error
˜
™
Startup concluded with error
˜
˜
*)
in addition the system-LED "ER" lights up on the basic system element
Error (startup aborted)
RY
ER
Note
Module defect
™
˜
*)
Exchange system element
PROM error (code)
™
˜
*)
Exchange system element
RAM error (data)
™
˜
*)
Exchange system element
Too little memory
™
§
*)
SICAM TOOLBOX II diagnosis
Parameter error
™
˜
*)
SICAM TOOLBOX II diagnosis
*)
in addition the system-LED "ER" lights up on the basic system element
Error (startup continued)
RY
ER
Note
Parameter error
˜
˜
*)
SICAM TOOLBOX II diagnosis
*)
in addition the system-LED "ER" lights up on the basic system element