Automation Units and Automation Networks
246
SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
6.2.2
SICAM AK 3 as Telecontrol Substation
•
Serial communication with the control system via IEC 60870-5-101
•
The communication to the process takes place with local peripherals or serial communica-
tions protocols (e.g.: MODBUS, …)
The local ethernet ports on CP-2016 or CP-2019 are not used in this application and thus
must be deactivated for security reasons.
The required parameter can be set on the BSE under
Network settings | IP address-
es
•
Mode of Ethernet ports
=
1 IP address (connected ports in switch mode)
•
Own IP address
=
0.0.0.0
•
Subnet mask
=
0.0.0.0
In this configuration both local ethernet interfaces are deactivated.
Substation Zone
Office Zone
Control Center Zone
SICAM AK 3
SICAM AK
SICAM AK
X3
X2
X1
X0
S
M
-2
5
5
1
IEC 60870-5-101
Control Center
IP-address:
172.17.0.22
Subnet mask: 255.255.0.0
Process
PRE2
CP-2016 or CP-2019
Netzwork settings| IP addresses
Own IP address
..........
....................
0.0.0.0
0.0.0.0
Subnet mask