17/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Mechanical installation
01.2002
3.3.3
Mounting SED2 drives with IP20/NEMA 0 rating
H
H
H
W
W
Frame size A
Frame size B
Frame sizes D, E and F
51
9
2
M0
1e
n
Hole spacing
Frame size
H in mm
W in mm
Mounting materials
Tightening
torque
A
160
* 187
-
* 56
2 x M4 bolts
2 x M4 nuts
2 x M4 spring lock washers
2 x M4 washers
or mounting on DIN rail
2.5 Nm
B
174
* 200
138
* 120
4 x M4 bolts
4 x M4 nuts
4 x M4 spring lock washers
4 x M4 washers
2.5 Nm
C
204
* 232
174
* 156
4 x M5 bolts
4 x M5 nuts
4 x M5 spring lock washers
4 x M5 washers
3.0 Nm
D
486
235
4 x M8 bolts
4 x M8 nuts
4 x M8 spring lock washers
4 x M8 washers
13 Nm
E
616.4
235
4 x M8 bolts
4 x M8 nuts
4 x M8 spring lock washers
4 x M8 washers
13 Nm
F
810
1110 with filter
300
4 x M8 bolts
4 x M8 nuts
4 x M8 spring lock washers
4 x M8 washers
25 Nm
* with footprint filter
A minimum clearance of 100 mm is required above and below each variable speed
drive.
Drilling plan for SED2
IP20
Note
.
.
.
.