34/126
Siemens Building Technologies
SED2 variable speed drives
CM1U5192en
HVAC Products
Electrical installation
01.2002
PE
L1
L2
L3
L1
DC+
B
DC+
B
U
V
L2
L3
W
DC-
B-
DC+
R+
View without cable entry guide
and without lower terminal connection plate
Mains voltage inputs
EMC filter
5192Z09en
4.3.6
Tightening torque for connection terminals
Frame size
A
B
C
D
E
F
Tightening torque
Nm
1.1
1.5
2.25
10 (max.) 10 (max.)
50
4.3.7
Cross-sections for power and motor cables
Input voltage range 200 V – 240 VAC, 3-phase
Output
rating
kW (hp)
Min. cross-
section of
supply cable
mm
2
(AWG)
Max. cross-
section of supply
cable
mm
2
(AWG)
Min. cross-
section of motor
cable
mm
2
(AWG)
Max. cross-
section of motor
cable
mm
2
(AWG)
0.37 (0.5)
1 (17)
2.5 (13)
1 (17)
2.5 (13)
0.55 (0.75)
1 (17)
2.5 (13)
1 (17)
2.5 (13)
0.75 (1)
1 (17)
2.5 (13)
1 (17)
2.5 (13)
1.1 (1.5)
1 (17)
6 (9)
1 (17)
6 (9)
1.5 (2)
1.5 (15)
6 (9)
1 (17)
6 (9)
2.2 (3)
2.5 (13)
6 (9)
1 (17)
6 (9)
3 (4)
4 (11)
10 (7)
1.5 (15)
10 (7)
4 (5)
4 (11)
10 (7)
4 (11)
10 (7)
5.5 (7.5)
4 (11)
10 (7)
4 (11)
10 (7)
7.5 (10)
10 (7)
35 (2)
10 (7)
35 (2)
Connection terminals of
SED2 frame size F, IP20,
with built-in EMC filter