CE1P2522E / 30.03.2000
Basic Documentation RVL470
Siemens Building Technologies
58/68
RVL469
Landis & Staefa Division
18. RVL469
18.1. Features and function
The RVL469 has been designed as a favourably-priced controller for the control of a
second heating circuit. It must always be used in connection with a partner unit. The
basic design of the RVL469 is very similar to that of the RVL470. The relevant functions
have been adopted.
18.2. Technical design
18.2.1. Type of plant
The RVL469 only offers plant type 1 of the RVL470, namely «Space heating with mixing
valve».
B9
A6/B5
B7
BUS (LPB)
2527S01
E1
A6
Room unit QAW50 or QAW70
E1
Load (room)
B1
Flow temperature sensor
LPB
Data bus
B5
Room temperature sensor
M1
Heating circuit pump
B7
Return temperature sensor
N1
Controller RVL469
B9
Outside sensor
Y1
Heating circuit mixing valve
18.2.2. Operation with a partner
Suitable partners
The following L & S controllers can be used as partners:
•
RVL470
•
RVL471
•
RVL472
•
RVL47
Each RVL469 requires one such partner. The plant type selected on the partner is of no
importance to the RVL469.
Addressing the partner
On the bus (LBP), the RVL469 must be located in the same segment as its partner. Its
device number must be one digit lower than that of the partner. If the addressing is not
correct, the RVL469 will not operate, or it will change to the passive mode.
Addressing example with two RVL470 and two RVL469:
Type of device
Segment number
Device number
A (RVL470)
1
1
B (RVL470)
1
3
C (RVL469)
1
2
D (RVL469)
1
4
In this example, controllers A and C and controllers B and D form one pair.