Siemens Building Technologies
Basic Documentation RVL470
CE1P2522E / 30.03.2000
Landis & Staefa Division
Communication
57/68
7
Second heating period, start
of NORMAL heating
Changes operating line 7 on the RVL470
8
Second heating period, start
of RECUCED heating
Changes operating line 8 on the RVL470
9
Third heating period, start of
NORMAL heating
Changes operating line 9 on the RVL470
10
Fourth heating period, start of
REDUCED heating
Changes operating line 10 on the RVL470
11
Entry weekdays 1...7
Changes operating line 39 on the RVL470
12
Entry time of day
Changes operating line 38 on the RVL470
13
Display of d.h.w. temperature Not available on the RVL470
14
Display of boiler temperature
(Only with plant types 2 and 5)
15
Display of flow temperature
(Only with plant types 1, 3, 4 and 6)
16
Holidays
RVL470 changes to STANDBY
17
Reset to default values
QAW70 default values are used
51
Bus address
Bus address to be entered on the room unit 1
52
Identification room unit
Display on operating line 196 of the RVL470
53
Operating lock on QAW70
No effect on RVL470
58
Type of setpoint display
No effect on RVL470
17.1.3.4. Overriding the QAW70 entries from the RVL470
If the RVL470 with a connected QAW70 is isolated from the mains network and then
reconnected, the following parameters on the QAW70 will be overwritten with the set-
tings made on the RVL470:
•
Time of day and weekday
•
Complete heating program
•
Room temperature setpoint of NORMAL heating
•
Room temperature setpoint of REDUCED heating
This means that the RVL470 is always the data master.
17.1.4. Combination with SYNERGYR central unit OZW30
Based on the room temperatures of the individual apartments, the central unit OZW30
(software version 3.0 or higher) generates a load signal. This signal is passed on via
LPB to the RVL470 where it produces an appropriate change of the flow temperature
setpoint.
17.2. Communication with other devices
The RVL470 offers the following communication choices:
•
Signalling the heat demand of several RVL470 to the heat generating equipment
•
Exchange of locking and forced signals
•
Exchange of measured values such as outside temperature, return temperature and
flow temperature as well as clock signals
•
Communication with other devices
•
Exchange of fault status signals
For detailed information about the communication via LPB, refer to the following pieces
of documentation:
•
Data sheet N2030E, "Basic System Data"
•
Data sheet N2032E, "Basic Engineering Data"