CE1P2522E / 30.03.2000
Basic Documentation RVL470
Siemens Building Technologies
20/68
Function block "Space heating"
Landis & Staefa Division
8.2.3.2. Switching the heating on
The heating will be switched on again only when all three of the following conditions are
satisfied:
•
The actual outside temperature has fallen 1 °C below the current ECO heating limit
•
The composite outside temperature has fallen 1 °C below the current ECO heating
limit
•
The attenuated outside temperature has fallen 1 °C below the "ECO day" heating limit
8.2.4. Operating modes and operational statuses
The ECO function is provided depending on the operating mode:
Operating mode or operational status
ECO function
Actual heating limit
Automatic mode
Active
ECO day or ECO night
Continuously REDUCED heating
Active
ECO night
Continuously NORMAL heating
Inactive
–
STANDBY
Active
ECO-night
Frost protection / holiday mode
Active
ECO-night
Manual operation
Inactive
–
8.3. Room temperature source
The room temperature source can be selected on operating line 65.
The following settings are possible:
Operating line 65
Room temperature source
0
No room temperature sensor
1
Room unit connected to terminal A6
2
Room temperature sensor connected to terminal B5
3
Average value of devices connected to terminals A6 and B5
A
Automatic selection
Line 65 also displays the room temperature source effectively used by the controller
(indicated by ACTUAL):
ACTUAL = 0
Controller uses no sensor
ACTUAL = 1
Controller uses the room unit connected to terminal A6
ACTUAL = 2
Controller uses the room temperature sensor connected to
terminal B5
ACTUAL = 3
Controller operates with the average value delivered by the devices
connected to terminals A6 and B5
8.4. Optimization
8.4.1. Definition and purpose
Operation is optimized. EN 12098 defines optimization as "automatic shifting of the
switch-on and switch-off points aimed at saving energy". This means that
•
switching on and heating up as well as switching off are controlled such that during
building occupancy times the required room temperature level will always be ensured
•
the smallest possible amounts of energy will be used to achieve this objective